Basic Overview of ET200 SP HA

Image
The high-performance I/O system SIMATIC ET 200SP HA – perfectly matched to the requirements of the process industry and with clear advantages wherever ruggedness and maximum availability are important in the process and manufacturing industry. Benefits Availability: Redundancy at the PROFINET interface (S2 or R1) Hot swapping during runtime station expansion possible during runtime Easy to Use: Compact modules with permanent wiring. One terminal block for all 24 V standard signals Tool-free connection system with push-in-terminals Compact Design Compact with up to 56 i/o modules per station High concentration of up to 32 channels on a module that is only 22.5 mm wide System-integrated power bus Seamless integration in SIMATIC PCS new PROFINET IO communication standard Functions Main functions Compact I/O modules Up to 32 channels on a module that is 22.5 mm wide Up to 56 modules per station Perfectly suited for applications in the field Installation up to hazardous zone 2 Extended temp

S7-1500 Program upload through unspecified CPU and upload from device software.

 Upload From Device Software-S7-1500


when upload as new station is not possible and we want to upload complete content of the "Program Blocks" folder with the PLC tags, PLC data types, Technology objects and any other folder from online CPU then we use option upload from device software. This can be used with plc in TIA portal.

Create a new step7(TIA) project and add s7-1500 unspecified CPU using Add new device function in TIA.


Click on the detect button to find the online CPU. If your connection is okay then you well the hardware details. Click recognize. Your offline plc hardware will be replaced with online configuration in TIA Project.

Now select go online from the tool bar. select all the proper setting required for connecting CPU and then press go online button.


When online connection is established, in project tree right click and select upload from device(software). All program from online CPU is updated in offline TIA project.

Kindly note complete hardware is not uploaded in this method.










Comments

Popular posts from this blog

Project Migration in TIA from Older version to TIA V17

S7-1500 Memory Concepts

Firmware Update of S7-1500 CPU/interface module, display and I/O modules.