Basic Overview of ET200 SP HA

Image
The high-performance I/O system SIMATIC ET 200SP HA – perfectly matched to the requirements of the process industry and with clear advantages wherever ruggedness and maximum availability are important in the process and manufacturing industry. Benefits Availability: Redundancy at the PROFINET interface (S2 or R1) Hot swapping during runtime station expansion possible during runtime Easy to Use: Compact modules with permanent wiring. One terminal block for all 24 V standard signals Tool-free connection system with push-in-terminals Compact Design Compact with up to 56 i/o modules per station High concentration of up to 32 channels on a module that is only 22.5 mm wide System-integrated power bus Seamless integration in SIMATIC PCS new PROFINET IO communication standard Functions Main functions Compact I/O modules Up to 32 channels on a module that is 22.5 mm wide Up to 56 modules per station Perfectly suited for applications in the field Installation up to hazardous zone 2 Extended temp

Basic Concept of Y link and its module.

Basics Of Y link structure and Its module

Y link is used to connect the Single DP salve system to Redundant Master DP system. It consist of Two IM 153-2 and Y couple with backplane bus. When DP slaves are connected to Y link then it forms the separate individual Profibus network.

The Y link creates a gateway from a redundant DP master system to a unilateral DP master system.
Below is the brief architecture of Y link:

 


Steps to incorporate in Hardware Configuration:


1. Select the IM from the hardware catlog


2. Drag and Drop on the Profibus network of H system and check the properties


3. Select wether to define as PA link or Profibus Y link as per below


4. Finally it will come as per below. Add single port DP slaves on the new network created.



Important Points

1. 
The Y Link 6ES7197-1LA12-0XA0 comprises the following hardware components:
Hardware component Article number
2 x IM 153-2 6ES7153-2BA70-0XB0
1 x Bus module IM/IM 6ES7195-7HD80-0XA0
1 x Y Coupler 6ES7197-1LB00-0XA0
1 x Bus module Y Coupler 6ES7654-7HY00-0XA0

2.
Earlier IM157 was used now IM153-2 is used for configuration.
Backplane compatibility with the New IM if replacing with Old is to be check.



Comments

Popular posts from this blog

Project Migration in TIA from Older version to TIA V17

S7-1500 Memory Concepts